Home inspection reportReport SAMPLE-TO-2611
(437) 227-6800contact@jbminspect.cajbminspect.ca
Real report · client details removed

Sample Home Inspection Report

Detached 1½-storey brick home · Toronto, Ontario

  • InterNACHI Certified Professional Inspector
  • PITI Level I Infrared
  • Drone roof survey
  • Thermal imaging
Prepared forName withheld (published with permission)
InspectionNovember 2026
InspectorJit Makim, CPI
ReportSAMPLE-TO-2611
Front of a detached 1½-storey brick home in Toronto with a white-sided gable, aluminum awnings and concrete front steps
68 findingswith 149 photos, drone and thermal images
Start with the priorities15 Safety, 30 Repair, 16 Maintenance, 7 MonitorMake a listFor contractors, your realtor or moving inFloor plansEvery finding marked by room
At a glance

What we found

Tap a tile to show only that priority.

Inspector's overview

This home is an older brick 1½-storey house that, according to the listing, has been owned by the same family for several decades. Much of it is original and has been maintained rather than renovated. The visible parts show conventional masonry and wood-frame construction. No conclusive major structural failure was found during this visual inspection, but much of the foundation and framing is hidden behind finishes, and the areas of floor movement and foundation deterioration need further assessment before their significance can be judged. Several items should be dealt with before you move in, and a few call for a tradesperson's assessment and quote before closing.

Life safety first

Two of the three smoke alarms did not work and no carbon monoxide (CO) alarms were found, although the house has a gas furnace. The dryer vents through a soft plastic duct (a fire risk), the garage door opener has no photo-eye sensors, and a capped pipe sticks up through the floor of the small upper room. Ontario requires working smoke alarms on every storey and outside sleeping areas, and, since 1 January 2026, CO alarms on every storey and next to sleeping areas in homes with a fuel-burning appliance. These are inexpensive to fix.

Electrical system needs an electrician's review

GFCI protection was not detected at either kitchen's counter, a failed GFCI outside, open-ground and reversed-polarity receptacles in five rooms, a mix of older and newer wiring with loose conductor ends above the panel, a full panel, makeshift wiring on top of the water heater and a scorched-looking receptacle behind the washer. Have a licensed electrical contractor review the whole system before closing; some insurers also ask about older wiring.

Water at the foundation and in the basement

The foundation wall in the closet under the basement stairs is flaking, with white mineral deposits, and gave a strongly elevated moisture-meter response. The main water shut-off valve in the same closet was leaking. Outside, the rear ground and patio slab slope toward the house, and the garage downspout empties toward its own foundation. The basement bathroom floor also gave elevated readings around a loose toilet. Fix the plumbing leaks and outdoor drainage first, then re-check the walls.

Heating and hot water are ageing

The furnace's age is not confirmed. A gas pressure-test tag dated December 2006 hints that it may be about 20 years old, and water was dripping at the furnace during the inspection. The electric water heater is dated 2005 (21 years) and the listing shows it is rented. Budget for the furnace, and confirm the water heater's rental terms and whether the contract transfers to you.

Roof is in fair shape; the chimney and service mast need work

The drone survey showed laminated asphalt shingles in serviceable condition, with one lifted shingle. The chimney has eroded mortar and a weathered crown. There is no active fireplace, but an open plastic vent pipe of unconfirmed purpose ends at the chimney top. The overhead electrical service mast that comes through the roof is rusting, a separate cable lies across the shingles, and the telephone and cable lines at the rear hang loose.

Attic and comfort

The attic behind the upper knee walls is in poor condition: displaced and stained insulation, torn paper and debris, and dark staining on the roof boards. The thermal camera showed cold areas in the upper bedroom walls and ceiling. Air sealing and new insulation would improve comfort and lower heating costs.

Next steps

Your action plan before closing

  1. Licensed electrical assessment before closingHave an ESA-licensed electrical contractor review the older wiring, the receptacle faults, the panel, the loose conductors and the scorched-looking receptacle. Ask for a written scope of corrections, a quote, and anything your insurer will need to know about the wiring.
  2. Moisture and drainage evaluationHave the leaking main water shut-off replaced, and have the damp foundation wall under the stairs, the rear patio that forms the cold-room roof, and the loose basement toilet assessed. Find out which areas need repair and whether anything should be opened up to look further.
  3. Gas, heating and chimney evaluationHave a TSSA-registered HVAC contractor find the source of the water at the furnace, inspect the furnace and its venting, confirm its age from the nameplate, and give you a realistic replacement budget.
  4. Floor movementAsk a qualified contractor to look at the bouncy floor areas from below where possible, and bring in a structural engineer if they find framing deterioration, excessive deflection or movement.
  5. Confirm how you will use the basementIf you plan to rent the basement as a separate unit, confirm permits, legal use, fire separation and exit requirements with the City of Toronto and the appropriate professionals before you commit.
  6. Safety corrections before you move inMany of the Safety items are quick and inexpensive: smoke and CO alarms, the receptacle cover plate, the range anti-tip bracket, the dryer duct and the garage-door sensors. Do these before moving in. The electrical wiring items are larger and come out of the assessment in step 1.

None of this means the house is a poor purchase. It lists the open questions to resolve before you are financially committed. This report does not estimate repair costs. Contractor quotes for the electrical, moisture, structural and heating items will be more reliable, and more useful in negotiation.

Make a list

Turn this report into the list you need

Each list can be copied, printed or saved as a PDF, emailed or sent by WhatsApp. Lists are made in your browser; nothing is uploaded.

For you

For your realtor

A list is a convenience copy. The full report holds the details, photos and limitations: read it before relying on any list. This report does not advise on price or negotiation.

Summary

All findings by priority

#Safety (15)WhereWho to call
21Water dripping at the furnaceUtility room: return side of the furnace and the floor beneathTSSA-registered HVAC contractor
37Smoke alarms not working; no carbon monoxide alarmsMain-floor hallway, upper floor, whole houseHomeowner, or an electrician for hard-wired alarms
38No GFCI protection detected at the kitchen countersMain-floor kitchen (both receptacles beside the sink) and basement kitchen (counter receptacles about 3 ft and 3.5 ft from the sink)Licensed electrician
39Exterior GFCI receptacle does not tripLeft side of the house, exterior wallLicensed electrician
40Open-ground and reversed-polarity receptaclesUpper bedroom 4, upper bedroom 3, small upper room, main-floor bedroom 2 (open ground); main-floor bedroom 1 (hot and neutral reversed)Licensed electrician
41Mixed and older wiring, loose conductors at the panelBasement utility room, at and above the electrical panelLicensed electrical contractor
42Makeshift wiring on top of the water heaterBasement utility room, top of the electric water heaterLicensed electrician
43Discoloured receptacle behind the washerBasement laundry area, behind the washing machineLicensed electrician
45Receptacle missing its cover plateBasement family room, lower side of the central columnHomeowner or electrician
49Capped pipe sticking up through the floorSmall upper room (1.58 × 1.16 m), carpeted floor near the wallTSSA-registered gas contractor
50Upper floor may lack an emergency escape windowUpper floor (bedrooms 3 and 4); also noted in main-floor bedroom 1Window contractor
51Dryer exhaust duct is soft plasticBasement laundry area, in the cabinet above the dryerHVAC contractor or appliance technician
61Range anti-tip bracket missing on the basement rangeBasement kitchen range (not confirmed on the main-floor range)Appliance installer or handyman
62Garage door opener has no photo-eye safety sensorsGarage vehicle doorGarage door technician
66Garage ceiling wiring is makeshift; roof sheathing stainedGarage ceilingLicensed electrician; roofer
#Repair (30)WhereWho to call
1Chimney: eroded mortar, weathered crown and uncapped ventBrick chimney, rear of the house, driveway sideMason; TSSA-registered gas contractor
2Overhead service mast rusting; loose cables on the roof and rear wallThrough-roof electrical service mast, front of the driveway-side slopeLicensed electrical contractor; Toronto Hydro; telephone and cable providers
3One lifted shingle; dark streaking on the shaded slopeMain roof, left (neighbour-side) slopeRoofer
7Front steps cracked; railings rusted at the posts (fall hazard)Front entry steps and landingConcrete contractor; railing or welding contractor
8Front door and window trim deterioratingFront of the house: door surround and front windowCarpenter or painter
9Exterior doors not sealing; front door hard to latchFront (main) entrance and side entranceDoor contractor or handyman
10Rear grading and patio slab direct water toward the houseRear of the house, around the raised concrete patio (the roof of the basement cold room)Landscaper; concrete or waterproofing contractor
11Mortar deterioration and loose cables on the rear wallRear brick wallMason
12Furnace vent pipes end low beside the drivewayDriveway (right) side, between the basement windowsTSSA-registered gas contractor
13Mail slot opens straight through the wallSide entrance landing (basement stairs)Handyman
14Gas meter and outside gas piping: rust and soil contactRight (driveway) side near the front, at the gas meter and along the foundationEnbridge Gas; TSSA-registered gas contractor
15Front downspout empties at the foundationRight (driveway) side, front corner of the houseHandyman or eavestrough contractor
18Damp, deteriorating foundation wall in the closet under the stairsBasement, closet under the stairs (water meter and main shut-off)Waterproofing contractor; plumber
19Basement cold room openings, damaged ceiling and wall depositsBasement cold room (under the rear patio)General contractor; electrician
20Bouncy floor areas and an unfinished floor transitionMain floor: kitchen (about 32 in / 81 cm inside the doorway), entrance-to-living-room transition, and just inside main-floor bedroom 1General contractor; flooring contractor
25Main water shut-off valve leaking (fix before closing)Basement, closet under the stairs, on the wall pipe beside the water meterPlumber
26Water heater past its expected lifeUtility roomPlumber or rental provider
27Loose toilet; elevated floor moisture readings in the basement bathroomBasement bathroomPlumber
28Corroded drains and valves: main-floor bathroom sinkMain-floor bathroom, under the sinkPlumber
29Basement bathroom sink: corroded drain, no shut-off valvesBasement bathroom, under the sinkPlumber
30Kitchen sinks: corroded valves and drain jointsUnder both kitchen sinksPlumber
31Laundry: corroded washer valves, old rubber hosesBasement laundry areaPlumber
32Main bathroom: tub seal, no exhaust fan, window sticksMain-floor bathroomTile contractor; electrician or HVAC contractor for the fan
47Attic insulation displaced, stained and below current levels; dark staining on the roof boardsAttic spaces behind the upper-floor knee wallsInsulation contractor; roofer if needed
52Old laundry exhaust fan open to the outdoorsBasement laundry areaElectrician or HVAC contractor
53Open hole in the wall behind the basement kitchen cabinetBasement kitchen, inside the upper cabinetGeneral contractor
54Living room window frame damaged; possible failed sealLiving room, front windowWindow contractor
63Garage block wall: open joint, cracked mortar, damp wallsGarage wallsMason
64Garage downspout empties toward the foundationGarage exterior, rear cornerHandyman or eavestrough contractor
65Garage doors and trim weathered; split door panelGarage pedestrian door, vehicle door and their trimCarpenter; garage door technician
#Maintenance (16)WhereWho to call
4Gutters hold debrisLeft-side eavestrough on the house; detached garage gutterHomeowner or handyman
16Driveway crackingAsphalt driveway beside the house and in front of the garagePaving contractor
17Wasp nest at the rear gableRear of the house, under the gable peakPest control
22Furnace age unconfirmed: service now and plan for replacementUtility roomTSSA-registered HVAC contractor
24Older mechanical thermostatMain floor, dining-area doorwayHVAC contractor or homeowner
34Outdoor faucet: shut off and drain for winterDriveway (right) side, by the side entranceHomeowner or plumber
35Cold room floor drain partly clogged and painted overBasement cold roomHomeowner or plumber
36Toilet tank depositsBasement bathroomHandyman
44Panel full; circuit directory incompleteBasement utility roomLicensed electrician
46Basement shower light not workingBasement bathroomHomeowner or electrician
48Attic access panels not insulated or weatherstrippedUpper bedroom 4 and the small upper roomHandyman or insulation contractor
55Main-floor bedroom 2: window caulking and closet wallMain-floor bedroom 2: window, and the closet wall shared with the bathroomHandyman; painter
56Upper bedroom 3: hole in the wall and a gap at the trimUpper bedroom 3, beside the windowHandyman
57Upper bedroom 4: window sill finish peelingUpper bedroom 4Painter
58Several windows stickMain-floor bathroom, basement bathroom, upper bedroom 3Handyman or window contractor
59Basement bathroom fan works only with the heat-lamp lightBasement bathroom ceilingElectrician
#Monitor (7)WhereWho to call
5Plumbing vent stacks and box vents ageingMain roofRoofer
6Garage roof shingles wornDetached garage roofRoofer
23Air conditioner appears to be an R-22 systemIndoor coil above the furnace; outdoor condenser at the rearHVAC contractor
33Water flow drops when two fixtures runMain-floor bathroom and basement bathroomPlumber
60Hairline crack in the living room ceilingLiving room ceilingPainter or plasterer
67Garage floor crackGarage floor, running to the entranceConcrete contractor if it changes
68Thermal imaging: cold areas in the upper bedroomsUpper bedrooms 3 and 4: sloped ceilings and knee wallsInsulation contractor

What the priorities mean

Safety
A hazard to people. Correct as soon as possible, and before moving in.
Repair
A defect that should be repaired by the trade named. Get a quote before closing where you can.
Maintenance
Routine upkeep, servicing or a minor fix.
Monitor
No repair needed now. Watch for change, or plan and budget for it.
Before you close

Questions, budget and conditions

Questions to ask the seller

Items to plan and budget for

Get contractor quotes; this report does not estimate costs.

Furnace replacement
Age unconfirmed, possibly about 20 years. Confirm it from the nameplate, service it now, and plan for replacement.
Water heater
21 years old and rented (per the listing). Ask the rental company to replace it, or budget for a buy-out and replacement.
Central air conditioner
Appears to be an R-22 system (refrigerant not confirmed); R-22 has been phased out. A refrigerant leak or major failure usually means replacing the system.
Electrical updates
GFCI protection, receptacle wiring corrections, cleanup at the panel, and possibly a larger panel or service.
Attic air sealing and insulation
Remove the damaged material, air-seal, then insulate to current levels.
Chimney repointing and crown
Repoint the mortar, repair the crown, and add a cap to the vent.
Basement wall moisture
Correct the drainage first; waterproofing work if the dampness continues.
Garage
Door safety sensors, the wood door and trim, block wall repairs and wiring.
Front steps and railings
Concrete repairs and rust treatment, or replacement of the railings.

Inspection conditions

Weather
Clear, with morning fog
Outdoor temperature
7.8 °C
Indoor temperature
22 °C
Occupancy
Vacant (furnished)
In attendance
Buyer's agent
Property type
Detached 1½-storey brick house with finished basement and detached garage
Approximate age
Not confirmed. Construction style suggests the late 1940s to 1950s.
Floor area
About 212 m² in total (basement 91 m², main floor 75 m², upper floor 46 m²), from the floor plan
Utilities
Water, power and gas on
Roof method
Drone (aerial photographs) plus ground level

Scope, standards and limitations

Scope. This was a visual, non-invasive inspection of the readily accessible systems and components of the home, done to give you a general understanding of its condition on the day of the inspection. It is not technically exhaustive and does not predict future conditions.

Standards. The inspection followed the InterNACHI Home Inspection Standards of Practice. A copy is available on request.

Limitations. Areas that were concealed, inaccessible, unsafe, or blocked by belongings or finishes could not be inspected. Systems were run only with their normal controls. Conditions can change after the inspection date. Where this report recommends further evaluation, have a qualified contractor do it before closing where possible.

Use of this report. This report was prepared for the client named on the cover, under the inspection agreement signed before the inspection, and is for the client's use only. It is not a warranty, guarantee or insurance policy. Anyone else who receives a copy should not rely on it and should arrange their own inspection.

Limitations specific to this inspection

Section 1 of 10

Roof, chimney and gutters

3 Repair1 Maintenance2 Monitor

About this system

Roof styleGable roof (1½ storey); separate gable roof on the detached garage.
CoveringLaminated (architectural) asphalt shingles on the house; asphalt shingles on the garage.
How inspectedDrone flight with close-up aerial photographs of every slope, chimney and penetration, plus ground-level viewing. We did not walk on the roof.
PenetrationsFour static box vents, two plumbing vent stacks with rubber boot flashings, a through-roof electrical service mast, and the brick chimney.
FlashingMetal step and counter flashing at the chimney (it looks fairly new); rubber boots at the stacks and the mast.
GuttersAluminum eavestroughs and downspouts.
General conditionThe house shingles lie flat, with normal granule wear for their age. We saw no missing or curled shingles in the aerial photos, apart from the one lifted shingle noted below. Ask the seller how old the roof is.
Main roof from the rear: laminated shingles and ridge
Main roof from the rear: laminated shingles and ridge
Driveway-side slope: box vents, plumbing stacks and chimney flashing
Driveway-side slope: box vents, plumbing stacks and chimney flashing
Left-side slope: more weathering and dark streaking on the shaded side
Left-side slope: more weathering and dark streaking on the shaded side

Findings (6)

1

Chimney: eroded mortar, weathered crown and uncapped ventBrick chimney, rear of the house, driveway side

Repair
What we found
Several mortar joints are eroded or open, mostly at mid-height and near the top, and at least one brick has a chipped or missing corner. The cement crown is rough and weathered, with an open joint around the sheet-metal box set into it. The top of that box is rusted. The house has no active fireplace, and the furnace appears to vent through the side wall (see the Heating section), yet a grey plastic vent pipe comes up through the box and ends open at the top. What it serves could not be confirmed; the connection inside was not accessible. The metal flashing at the base looks newer and intact; a patch of black sealant at the upslope corner should be kept in good repair.
Why it matters
Water that gets into open joints and a cracked crown freezes and spalls the brick, and over time can loosen the top courses. Rain, snow and animals can get into an open pipe, and an abandoned vent left open is a path for water into the house.
What to do
Have a mason repoint the open joints and repair or rebuild the crown. Have a TSSA-registered gas contractor find out what, if anything, still uses this vent and confirm it is the right type with a proper termination. If nothing vents there any more, have the chimney capped off.
Who to call
Mason; TSSA-registered gas contractor
Open and eroded mortar joints, mid-height
Photo 1.1Open and eroded mortar joints, mid-height
Weathered crown, rusted box and the open vent pipe
Photo 1.2Weathered crown, rusted box and the open vent pipe
Chimney base flashing and the plumbing stack beside it
Photo 1.3Chimney base flashing and the plumbing stack beside it
2

Overhead service mast rusting; loose cables on the roof and rear wallThrough-roof electrical service mast, front of the driveway-side slope

Repair
What we found
The overhead power line attaches to a steel mast that comes up through the roof. The mast has lost much of its paint and is rusting along its length. Its base flashing appears seated, and drip loops are present at the top. A separate low cable, probably telephone or cable TV, runs across the shingles and close to the vents and plumbing stack. A second set of overhead lines comes from the utility pole in the rear lane and attaches to the rear wall just below the gable. These look like telephone and cable TV lines, not a second power supply: they are single round cables, a coax connector is visible where they come down the wall, and there is no second mast, drip loop or meter at the rear. They pass close in front of the upper rear window and then hang loosely down the brick.
Why it matters
The mast carries the pull of the service wires, and corrosion weakens it. A cable resting on the roof wears the shingle surface and can be snagged during roof work.
What to do
Have a licensed electrical contractor (ESA) check the mast's condition, bracing and flashing and repaint or replace it as needed. Any work on the service wires must be coordinated with Toronto Hydro. Ask Toronto Hydro or the electrician to confirm that the house has only the one electrical service and that the rear lines are communication cables. Ask the telephone and cable providers to re-route the cable off the roof, keep their rear drops clear of the upper window, fasten the cables to the wall properly and remove any that are no longer used. Do not touch any overhead wires yourself.
Who to call
Licensed electrical contractor; Toronto Hydro; telephone and cable providers
Rusting mast, drip loops and the cable crossing the roof
Photo 2.1Rusting mast, drip loops and the cable crossing the roof
Service drop leaving the mast toward the street
Photo 2.2Service drop leaving the mast toward the street
Rear lines attaching below the gable, passing in front of the upper window
Photo 2.3Rear lines attaching below the gable, passing in front of the upper window
3

One lifted shingle; dark streaking on the shaded slopeMain roof, left (neighbour-side) slope

Repair
What we found
One shingle near the middle of the left slope shows a dark gap along its edge, so it appears lifted, creased or unsealed. This slope gets less sun and has more dark streaking (algae) than the driveway side.
Why it matters
A lifted shingle can blow off in high wind and let water reach the roof deck. The streaking is mainly cosmetic.
What to do
Have a roofer reseal or replace the lifted shingle and check the surrounding courses. Zinc strips at the ridge can limit future streaking if you want.
Who to call
Roofer
Lifted or unsealed shingle edge (dark line, centre right)
Photo 3.1Lifted or unsealed shingle edge (dark line, centre right)
4

Gutters hold debrisLeft-side eavestrough on the house; detached garage gutter

Maintenance
What we found
The left-side eavestrough on the house holds debris and dark residue. The garage gutter is packed with pine needles and leaves.
Why it matters
Blocked gutters overflow next to the walls, which adds to the moisture problems found at the foundation and in the garage.
What to do
Clean all gutters and downspouts each spring and fall, and check that the water flows to the downspouts.
Who to call
Homeowner or handyman
Debris in the left-side eavestrough
Photo 4.1Debris in the left-side eavestrough
Garage gutter full of needles and leaves
Photo 4.2Garage gutter full of needles and leaves
5

Plumbing vent stacks and box vents ageingMain roof

Monitor
What we found
The steel plumbing vent stack beside the chimney is rusted, and one box vent is lightly dented. The rubber boots around the stacks appear sealed.
Why it matters
Rubber boots crack with age and are a common source of small leaks.
What to do
Have the boots and vents checked whenever the roof is serviced, and replace them if they crack or lift.
Who to call
Roofer
Two plumbing stacks with rubber boots; one rusted
Photo 5.1Two plumbing stacks with rubber boots; one rusted
6

Garage roof shingles wornDetached garage roof

Monitor
What we found
The garage shingles show granule loss and surface wear consistent with an older roof covering.
Why it matters
Worn shingles lose their ability to shed water; the dark staining under the garage roof boards (see Garage) may be related.
What to do
Plan to re-shingle the garage roof in the next few years. Have a roofer check it sooner if the interior staining shows active wetness.
Who to call
Roofer
Garage roof edge: worn shingles
Photo 6.1Garage roof edge: worn shingles
Garage roof edge, another section
Photo 6.2Garage roof edge, another section
Section 2 of 10

Exterior and grounds

9 Repair2 Maintenance

About this system

Wall coveringBrick masonry, with siding at the gables and a parged (stucco-finished) foundation above grade. Aluminum awnings over most windows and doors.
Driveway and walksAsphalt driveway along the side of the house to the detached garage; concrete front walk and steps.
RearRaised concrete patio with steps. The basement cold room sits underneath it.
GradingFront and sides slope away from the house. The rear slopes toward the house (see finding).
Exterior doorsFront entrance with storm door; side entrance on the driveway side.
Front
Front
Driveway (right) side
Driveway (right) side
Rear
Rear
Left side
Left side

Findings (11)

7

Front steps cracked; railings rusted at the posts (fall hazard)Front entry steps and landing

Repair
What we found
The concrete steps are cracked, and some step sections have separated at the joints. The metal railings are rusted at the post bases, where they enter the concrete, and at several welded joints; paint is peeling.
Why it matters
These are trip hazards, and freeze-thaw cycles widen the cracks. Rust at the post bases can weaken the railing's anchorage, which is a fall hazard if the railing gives way.
What to do
Check that both railings are firm before relying on them. Have a concrete contractor repair the steps and a qualified contractor repair, refinish or replace the railings.
Who to call
Concrete contractor; railing or welding contractor
Cracked and separated step sections
Photo 7.1Cracked and separated step sections
Front steps overview
Photo 7.2Front steps overview
Rust at the railing post base and joints
Photo 7.3Rust at the railing post base and joints
Rusted balusters at the lower step
Photo 7.4Rusted balusters at the lower step
8

Front door and window trim deterioratingFront of the house: door surround and front window

Repair
What we found
Paint is peeling and the wood is weathered at the front door casing and pilasters, especially at their bases, and around the front window. The storm door is older.
Why it matters
Bare wood absorbs water and rots. Given the age of the house, the old paint layers may contain lead.
What to do
Probe the wood and replace any soft sections, then prime, paint and seal the joints. Have older paint tested before you scrape or sand it, and use lead-safe practices. Check that the storm door's latch, closer and seals work properly.
Who to call
Carpenter or painter
Front door surround: peeling paint at the bases
Photo 8.1Front door surround: peeling paint at the bases
Front window trim
Photo 8.2Front window trim
9

Exterior doors not sealing; front door hard to latchFront (main) entrance and side entrance

Repair
What we found
The main entrance door has worn or missing weatherstripping and does not latch easily. The side entrance door also lacks effective weatherstripping and has an older surface-mounted lock.
Why it matters
Drafts, heat loss and possible water entry. A door that does not latch reliably is also a security concern.
What to do
Adjust the doors and their hardware and replace the weatherstripping. Make sure all locks can be opened from inside without a key.
Who to call
Door contractor or handyman
Main entrance
Photo 9.1Main entrance
Side entrance
Photo 9.2Side entrance
Thermal: cold edges along the bottom and latch side of the side door
Photo 9.3Thermal: cold edges along the bottom and latch side of the side door
10

Rear grading and patio slab direct water toward the houseRear of the house, around the raised concrete patio (the roof of the basement cold room)

Repair
What we found
The ground at the rear slopes toward the foundation. The joint where the patio slab meets the soil and the house wall is open, with moss and plants growing in it, and leaves are packed against the slab edge. There is a long crack in the slab.
Why it matters
Water that collects here can soak down along the foundation. The slab is also the roof of the cold room below, which has peeling paint and mineral deposits; the drainage here may contribute, but the exact route water takes into the cold room could not be established.
What to do
Regrade so that the soil slopes away from the house for at least 1.8 m (6 ft), and clear the debris. Because the patio slab is the cold-room roof, have a concrete or waterproofing contractor assess its waterproofing, joints, cracks and drainage as a whole, rather than only sealing the visible cracks.
Who to call
Landscaper; concrete or waterproofing contractor
Rear yard sloping toward the house and patio
Photo 10.1Rear yard sloping toward the house and patio
Open joint and crack at the slab edge
Photo 10.2Open joint and crack at the slab edge
Slab-to-step joint and edge wear
Photo 10.3Slab-to-step joint and edge wear
11

Mortar deterioration and loose cables on the rear wallRear brick wall

Repair
What we found
Mortar joints are eroded and recessed in several areas, and the brick is discoloured. Cables run loose across the face of the wall. The brick arches and sealant around the basement windows are weathered.
Why it matters
Open joints let water into the wall, and freeze-thaw damage follows.
What to do
Have a mason repoint the deteriorated joints and reseal around the windows. Have the cable owners fasten their cables properly and seal any wall openings.
Who to call
Mason
Rear wall: discoloured brick and loose cables
Photo 11.1Rear wall: discoloured brick and loose cables
Eroded mortar joints
Photo 11.2Eroded mortar joints
Recessed and cracked joints
Photo 11.3Recessed and cracked joints
12

Furnace vent pipes end low beside the drivewayDriveway (right) side, between the basement windows

Repair
What we found
Two black plastic pipes come out of the parged foundation between two basement windows: an upper pipe with a downturned gooseneck and a lower elbow pointing down. Warm exhaust was coming out during the inspection, so this is not an old oil-tank vent. The furnace is a high-efficiency type that uses two plastic pipes, so these appear to be its exhaust and combustion-air intake. Their ends are only roughly 30 to 45 cm above the asphalt.
Why it matters
Gas appliance vents must stay above the snow line and keep set distances from windows and other openings. Snow plowed or drifting along the driveway can block them and shut the furnace down, and exhaust close to an openable window can be drawn back inside. The vent pipe must also be the type certified for the furnace.
What to do
Have a TSSA-registered gas contractor confirm that these terminations meet the furnace instructions and CSA B149.1 (height above grade and snow, distance from the windows, protection from vehicles) and that the pipe is the certified type, and raise or relocate them if needed. Until then, keep them clear of snow all winter.
Who to call
TSSA-registered gas contractor
Exhaust and intake pipes close to the driveway surface
Photo 12.1Exhaust and intake pipes close to the driveway surface
Position between the two basement windows
Photo 12.2Position between the two basement windows
13

Mail slot opens straight through the wallSide entrance landing (basement stairs)

Repair
What we found
The wall-mounted mailbox passes right through the exterior wall. Its foam lining is broken and gapped, and the opening is barely insulated or weatherstripped. The damage could be from pests.
Why it matters
Drafts, heat loss and an entry point for insects and mice.
What to do
Insulate and seal the enclosure, weatherstrip the inner door, and watch for signs of pests.
Who to call
Handyman
Inner mailbox door
Photo 13.1Inner mailbox door
Damaged foam lining inside
Photo 13.2Damaged foam lining inside
14

Gas meter and outside gas piping: rust and soil contactRight (driveway) side near the front, at the gas meter and along the foundation

Repair
What we found
The gas riser at the meter goes into the ground in soil and plants, with wire wrapped around it and some rust at grade. The steel gas pipe that runs along the foundation from the meter to where it enters the house is rusted along much of its length. A downspout extension rests against this pipe.
Why it matters
Rust weakens gas piping over time, especially where it touches soil and stays damp. Anything leaning on or knocking the piping stresses its joints.
What to do
Clear the soil, plants and debris from around the meter and riser and keep the area clear. Ask Enbridge Gas to check the riser and meter at grade, since the gas utility owns them. Have a TSSA-registered gas contractor clean, inspect and repaint the house piping, and re-route the downspout so nothing rests on the pipe. If you ever smell gas, leave the house and call Enbridge's emergency line from outside.
Who to call
Enbridge Gas; TSSA-registered gas contractor
Gas riser in soil and plants at the meter
Photo 14.1Gas riser in soil and plants at the meter
Rusted gas pipe along the foundation, with the downspout resting on it
Photo 14.2Rusted gas pipe along the foundation, with the downspout resting on it
Meter, piping and downspout extension
Photo 14.3Meter, piping and downspout extension
15

Front downspout empties at the foundationRight (driveway) side, front corner of the house

Repair
What we found
The downspout ends right at the base of the wall with no extension, and its bottom is crushed.
Why it matters
Roof water dumped at the foundation soaks down beside the basement wall, adding to the basement moisture found inside.
What to do
Repair the downspout and add an extension that carries water at least 1.8 m (6 ft) from the house, away from the neighbouring property and the gas meter.
Who to call
Handyman or eavestrough contractor
Crushed downspout ending at the wall
Photo 15.1Crushed downspout ending at the wall
16

Driveway crackingAsphalt driveway beside the house and in front of the garage

Maintenance
What we found
There is cracking across the driveway, including in front of the garage.
Why it matters
Water that gets into the cracks freezes and breaks up the asphalt.
What to do
Seal the cracks, and resurface the driveway as it ages.
Who to call
Paving contractor
Cracks along the side driveway
Photo 16.1Cracks along the side driveway
Cracking in front of the garage
Photo 16.2Cracking in front of the garage
17

Wasp nest at the rear gableRear of the house, under the gable peak

Maintenance
What we found
There is a wasp nest under the peak of the rear gable.
Why it matters
Stings, and possible nesting in the soffit.
What to do
Have a pest control service remove it.
Who to call
Pest control
Nest under the gable peak
Photo 17.1Nest under the gable peak
Section 3 of 10

Structure, foundation and basement moisture

3 Repair

About this system

FoundationConcrete block, seen in the closet under the stairs, the utility room and the cold room. Most basement walls are finished.
Floor framingWood joists with plank subfloor, seen in the utility room and closet.
Roof framingWood rafters with board sheathing, seen from the attic access openings.
WallsBrick masonry.
LimitsFinished walls and ceilings hide most of the structure. We judged its condition from what was visible and from the floors, walls and openings.

Findings (3)

18

Damp, deteriorating foundation wall in the closet under the stairsBasement, closet under the stairs (water meter and main shut-off)

Repair
What we found
The block foundation wall is in poor condition: the coating is flaking, the surface is spalling and crusty, and there are white mineral deposits (efflorescence) and dark staining that may be mould. A pinless moisture meter gave its maximum reading (100 on its relative scale) at several spots, against about 20 on similar walls elsewhere in the basement.
Why it matters
The deposits, staining and flaking show this wall has had repeated moisture exposure. A pinless meter gives a relative reading, not a measured moisture content, so the high readings show this area is much damper than the comparison areas but do not by themselves confirm how much water is present or whether it is entering now. Ongoing dampness breaks down the block surface and can support mould. Two possible sources are close by: the leaking main water valve in this closet, and the poor drainage outside.
What to do
First repair the leaking valve and correct the outdoor grading and downspouts. Then have a waterproofing contractor assess the wall. Have any mould cleaned up by a qualified remediator, and re-test the moisture after the repairs.
Who to call
Waterproofing contractor; plumber
Spalling, flaking block wall
Photo 18.1Spalling, flaking block wall
Crusty surface and efflorescence
Photo 18.2Crusty surface and efflorescence
Pinless meter at the top of its relative scale
Photo 18.3Pinless meter at the top of its relative scale
The closet: meter, valve and affected wall
Photo 18.4The closet: meter, valve and affected wall
Thermal: cooler, blotchy areas on the same wall (about 7–11 °C)
Photo 18.5Thermal: cooler, blotchy areas on the same wall (about 7–11 °C)
19

Basement cold room openings, damaged ceiling and wall depositsBasement cold room (under the rear patio)

Repair
What we found
Near the ceiling, an opening with a round metal duct leading outside is covered only with loose plastic. Along one wall the ceiling finish is broken open, exposing wiring and a pipe, and some of the wiring is loose. The block walls have peeling paint and white mineral deposits. The door from the finished basement is not weatherstripped.
Why it matters
The cold room is an unheated space that shares a wall with the finished basement. Unsealed openings let in cold air, moisture and pests, and the deposits show the walls have been exposed to moisture. Whether it comes through the walls, the slab joints above or both was not established.
What to do
Find out what the duct was for. Close it properly or fit a hood with a damper and screen. Repair the ceiling, and have an electrician secure the wiring. Weatherstrip and insulate the cold room door. Include the cold room in the patio-slab assessment (see the related finding), and monitor the walls after the drainage is corrected.
Who to call
General contractor; electrician
Duct opening covered with plastic
Photo 19.1Duct opening covered with plastic
Broken ceiling finish and exposed wiring
Photo 19.2Broken ceiling finish and exposed wiring
Peeling paint and deposits on the block
Photo 19.3Peeling paint and deposits on the block
Cold room door, no weatherstripping
Photo 19.4Cold room door, no weatherstripping
20

Bouncy floor areas and an unfinished floor transitionMain floor: kitchen (about 32 in / 81 cm inside the doorway), entrance-to-living-room transition, and just inside main-floor bedroom 1

Repair
What we found
The floor has noticeable bounce at three spots. At the entrance-to-living-room transition there is no proper threshold: the joint is taped, the edges are exposed, and the area is stained.
Why it matters
Bounce can come from long joist spans or framing that is not stiff enough, a loose or deteriorated subfloor, or framing that has been notched or damaged. The cause could not be seen because the basement ceiling is finished. The open transition is a trip hazard.
What to do
Have a qualified contractor evaluate the framing from below where it can be reached, and involve a structural engineer if they find significant movement or deterioration. Install a proper transition strip. If the old vinyl flooring at the entrance is to be removed, have it tested for asbestos first, given its age.
Who to call
General contractor; flooring contractor
Kitchen: bounce about 32 in (81 cm) from the doorway
Photo 20.1Kitchen: bounce about 32 in (81 cm) from the doorway
Taped entrance-to-living-room transition
Photo 20.2Taped entrance-to-living-room transition
Section 4 of 10

Heating, cooling and ventilation

1 Safety2 Maintenance1 Monitor

About this system

HeatingGas-fired high-efficiency (condensing) forced-air furnace, Carrier Performance 95, with ductwork. It has two black plastic vent pipes that appear to run out through the driveway-side wall, and its condensate drains through clear tubing to the floor drain. There is no active fireplace.
Approximate ageNot confirmed. A gas pressure-test tag dated December 2006 marked "furnace only" may relate to its installation, but a tag does not prove the installation or manufacture date. The nameplate or service records will confirm it.
HumidifierAprilaire bypass humidifier on the return plenum, connected with flexible duct and a summer/winter damper.
CoolingCentral air conditioner: indoor coil above the furnace (marked R-22; the system's refrigerant was not confirmed) and an outdoor condenser at the rear corner by the patio. Not run: it was 7.8 °C outside, and running the compressor below about 15 °C can damage it.
Other heatAn electric baseboard heater in the basement family room. Whether it is in use was not confirmed.
ThermostatOlder round mechanical thermostat at the main-floor dining-area doorway. Operated with its normal controls; the furnace responded.
Carrier Performance 95 furnace, humidifier and coil
Carrier Performance 95 furnace, humidifier and coil
Outdoor AC condenser
Outdoor AC condenser
Main thermostat
Main thermostat

Findings (4)

21

Water dripping at the furnaceUtility room: return side of the furnace and the floor beneath

Safety
What we found
Water was dripping down the return side of the furnace and onto the floor during the inspection. The floor and nearby drain piping are stained, which suggests it has happened before. The furnace is a condensing type, which makes water as it runs. Its condensate tubing, the air-conditioning coil drain and the humidifier drain all run as loose clear tubes to the floor drain beside it. A leaking condensate connection or the humidifier are the most likely sources.
Why it matters
Water around a gas appliance and its electrical parts can cause electrical faults, rust the furnace and ducts, and lead to mould.
What to do
Shut off the humidifier's water supply until it is serviced. Have a TSSA-registered HVAC contractor find and fix the source, check the condensate trap and tubing, secure the tubes into the drain, service the humidifier and change its pad, and check the furnace for water damage.
Who to call
TSSA-registered HVAC contractor
Humidifier and return plenum above the furnace
Photo 21.1Humidifier and return plenum above the furnace
Water and staining at the floor
Photo 21.2Water and staining at the floor
Return-side piping and duct where water was running
Photo 21.3Return-side piping and duct where water was running
Loose condensate and drain tubes at the floor drain
Photo 21.4Loose condensate and drain tubes at the floor drain
22

Furnace age unconfirmed: service now and plan for replacementUtility room

Maintenance
What we found
A gas pressure-test tag dated December 2006 is attached, which may mean the furnace is about 20 years old, but a tag does not establish its installation or manufacture date. We found no service record, and the age was not confirmed from the nameplate. Paint cans and other stored items are right against the side of the furnace.
Why it matters
Gas furnaces usually last 15 to 25 years. Older units become less efficient and less reliable, and a cracked heat exchanger is a CO risk. Flammable products stored beside a gas appliance are a fire risk and block service access.
What to do
Move the paint and stored items away from the furnace. Ask the seller for the nameplate model and serial number or service records to confirm the age. Have it serviced and safety-checked, including a combustion and CO test, and budget for replacement. Fit CO alarms (see Electrical).
Who to call
TSSA-registered HVAC contractor
Ontario gas pressure-test tag, December 2006
Photo 22.1Ontario gas pressure-test tag, December 2006
Paint cans stored against the furnace
Photo 22.2Paint cans stored against the furnace
23

Air conditioner appears to be an R-22 systemIndoor coil above the furnace; outdoor condenser at the rear

Monitor
What we found
The indoor coil is marked "R-22 TXV", so the system appears to be designed for R-22. The rating label on the outdoor condenser has faded and cannot be read, so the refrigerant actually in the system was not confirmed. The system was not run because of the cold weather, so its operation was not checked.
Why it matters
R-22 has been phased out in Canada. It is increasingly scarce and expensive, so if this is an R-22 system, a refrigerant leak or major failure usually means replacing both the outdoor unit and the indoor coil.
What to do
Ask the seller how old the system is and for service records. Have an HVAC contractor confirm the refrigerant and test the system at the start of the cooling season, and budget for replacement.
Who to call
HVAC contractor
Indoor coil marked "R-22 TXV"
Photo 23.1Indoor coil marked "R-22 TXV"
Outdoor condenser; label faded
Photo 23.2Outdoor condenser; label faded
24

Older mechanical thermostatMain floor, dining-area doorway

Maintenance
What we found
The thermostat is an older round mechanical type. It operated the furnace normally.
Why it matters
Many older mechanical thermostats contain a small mercury switch. A programmable or smart thermostat would also give better comfort and lower heating costs.
What to do
Consider a programmable thermostat compatible with the furnace and air conditioner. If the old one contains mercury, take it to a household hazardous waste depot; do not throw it in the garbage.
Who to call
HVAC contractor or homeowner
Round mechanical thermostat
Photo 24.1Round mechanical thermostat
Section 5 of 10

Plumbing

8 Repair3 Maintenance1 Monitor

About this system

Water supplyMunicipal. The main shut-off valve and water meter are in the closet under the basement stairs.
Supply pipingCopper where visible.
Drain pipingCast iron and ABS plastic where visible.
Water heaterElectric tank, Giant "Ultra Cascade" 152E-3F8M-TH, 240 V, 4,500 W, manufactured July 2005 (about 21 years old). The listing shows it is under a rental contract.
GasGas meter and main gas shut-off on the right (driveway) side of the house, near the front.
FixturesMain-floor bathroom (tub and shower), basement bathroom (shower), two kitchens and a laundry sink.
Water heater
Water heater
Data plate: Giant 152E-3F8M-TH, 240 V, dated 0713 / 2005
Data plate: Giant 152E-3F8M-TH, 240 V, dated 0713 / 2005

Findings (12)

25

Main water shut-off valve leaking (fix before closing)Basement, closet under the stairs, on the wall pipe beside the water meter

Repair
What we found
The main shut-off is an older valve with heavy green corrosion, and it was actively leaking during the inspection.
Why it matters
This is the valve you rely on in a plumbing emergency, and old corroded valves often seize or leak worse when they are turned. The leak is also wetting the foundation wall right beside it.
What to do
Treat this as a before-closing item: until it is replaced you may not be able to shut off the water in an emergency. Have a plumber replace it with a full-port ball valve and check the meter connections at the same visit.
Who to call
Plumber
Corroded main valve
Photo 25.1Corroded main valve
Valve on the supply line
Photo 25.2Valve on the supply line
Closet with the meter and main valve
Photo 25.3Closet with the meter and main valve
26

Water heater past its expected lifeUtility room

Repair
What we found
The electric water heater was made in 2005. There is green corrosion on the copper fittings above it and staining on the wall behind.
Why it matters
Tank water heaters usually last 10 to 15 years, and an old tank can leak without warning.
What to do
The listing shows it is rented, so ask the rental company to replace it; if you buy it out instead, budget to replace it soon. Have a plumber check the fittings and the temperature-and-pressure relief valve and its discharge pipe. The wiring on top of the tank is a separate safety item (see Electrical).
Who to call
Plumber or rental provider
Data plate dated July 2005
Photo 26.1Data plate dated July 2005
Top of the tank: piping, valves and fittings
Photo 26.2Top of the tank: piping, valves and fittings
Corroded fittings above the tank
Photo 26.3Corroded fittings above the tank
27

Loose toilet; elevated floor moisture readings in the basement bathroomBasement bathroom

Repair
What we found
The toilet rocked when gently checked. The pinless moisture meter gave elevated relative readings, near the top of its scale, over most of the tiled floor, including around the toilet, compared with about 9 to 10 on similar tile elsewhere (three areas were tested).
Why it matters
A loose toilet can break its seal at the floor, and leaks under tile go unseen. The readings warrant investigation, but they do not by themselves prove there is water beneath the tiles or identify the source.
What to do
Have a plumber remove the toilet, inspect the flange, the seal and the accessible floor construction, determine whether there is concealed moisture or damage, and re-secure the toilet.
Who to call
Plumber
Toilet that moves at the base
Photo 27.1Toilet that moves at the base
Elevated relative reading on the floor tile
Photo 27.2Elevated relative reading on the floor tile
Readings taken across the floor
Photo 27.3Readings taken across the floor
28

Corroded drains and valves: main-floor bathroom sinkMain-floor bathroom, under the sink

Repair
What we found
The sink trap and tailpiece are heavily corroded, with mineral crust at the joints. Both supply shut-off valves are corroded.
Why it matters
Corroded drain parts eventually leak, and corroded valves may not shut off when you need them.
What to do
Replace the trap, tailpiece and both shut-off valves.
Who to call
Plumber
Corroded trap and tailpiece
Photo 28.1Corroded trap and tailpiece
Corroded supply valve
Photo 28.2Corroded supply valve
Second supply valve
Photo 28.3Second supply valve
29

Basement bathroom sink: corroded drain, no shut-off valvesBasement bathroom, under the sink

Repair
What we found
The drain tailpiece and trap are corroded. The supply lines are capped and have no working shut-off valves, the wall openings around the pipes are rough and unsealed, and there is dark spotting under the basin.
Why it matters
Leak risk, and nowhere to turn off this fixture's water locally.
What to do
Install shut-off valves, replace the corroded drain parts, and seal the wall openings.
Who to call
Plumber
Under the basement bathroom sink
Photo 29.1Under the basement bathroom sink
30

Kitchen sinks: corroded valves and drain jointsUnder both kitchen sinks

Repair
What we found
Basement kitchen: the shut-off valves and copper supply pipes are corroded, and the drain passes through the wall with an unsealed gap. Main-floor kitchen: there is corrosion and residue at the metal drain joints and staining in the cabinet, which suggests past slow leaks.
Why it matters
Leaks under sinks often go unnoticed and damage the cabinet and floor.
What to do
Run water and check both drains for leaks. Replace the corroded valves, connectors and drain parts, and seal the wall opening.
Who to call
Plumber
Basement kitchen: corroded valves and copper
Photo 30.1Basement kitchen: corroded valves and copper
Basement kitchen supply line
Photo 30.2Basement kitchen supply line
Main-floor kitchen drain: corrosion and residue
Photo 30.3Main-floor kitchen drain: corrosion and residue
31

Laundry: corroded washer valves, old rubber hosesBasement laundry area

Repair
What we found
The washer supply valves are corroded and the old rubber supply hoses are worn. The laundry sink's supply valves and copper joints are also corroded, and the drain opening in the wall is rough and unsealed.
Why it matters
A burst washer hose can flood a basement within minutes.
What to do
Replace the valves and fit braided stainless-steel hoses. Turn the washer valves off when the machine is not in use. Seal the drain opening.
Who to call
Plumber
Washer valves and old rubber hoses
Photo 31.1Washer valves and old rubber hoses
Corrosion at the washer valve
Photo 31.2Corrosion at the washer valve
Laundry sink supply valves
Photo 31.3Laundry sink supply valves
Unsealed drain opening in the wall
Photo 31.4Unsealed drain opening in the wall
32

Main bathroom: tub seal, no exhaust fan, window sticksMain-floor bathroom

Repair
What we found
The caulking and grout at the tub-to-floor and tub-to-wall joints are worn and open in places, with dark areas near the right end. The paint and wood at the bottom of the door casing are damaged. There is no exhaust fan, and the window is hard to open.
Why it matters
Water gets under the tile at open joints. Without a fan, and with a window that is hard to open, shower moisture stays in the room and the walls next to it, which fits the moisture marks in the next-door bedroom closet.
What to do
Re-grout and re-caulk the tub. Probe the door casing and repair it. Install an exhaust fan vented to the outside, and free up the window.
Who to call
Tile contractor; electrician or HVAC contractor for the fan
Open joint at the tub and the damaged casing
Photo 32.1Open joint at the tub and the damaged casing
Main bathroom
Photo 32.2Main bathroom
33

Water flow drops when two fixtures runMain-floor bathroom and basement bathroom

Monitor
What we found
In both bathrooms, the flow at the faucet dropped noticeably when a second fixture was turned on.
Why it matters
This is common with older or undersized supply piping and a partly closed or failing main valve.
What to do
Ask the plumber to check the supply piping and the water pressure when replacing the main valve.
Who to call
Plumber
Basement bathroom: one faucet running
Photo 33.1Basement bathroom: one faucet running
Reduced flow with a second fixture on
Photo 33.2Reduced flow with a second fixture on
34

Outdoor faucet: shut off and drain for winterDriveway (right) side, by the side entrance

Maintenance
What we found
There is an older-style outdoor faucet on the foundation by the side entrance. Whether it is a frost-free type was not confirmed.
Why it matters
A faucet or pipe left full of water can freeze and split in winter, and the leak often shows up inside the basement wall.
What to do
Before freezing weather, close the indoor shut-off for this faucet, open the outside faucet to drain it, and disconnect any hose. Consider replacing it with a frost-free faucet.
Who to call
Homeowner or plumber
Outdoor faucet by the side entrance
Photo 34.1Outdoor faucet by the side entrance
35

Cold room floor drain partly clogged and painted overBasement cold room

Maintenance
What we found
Several holes in the floor-drain grate are clogged, and the grate has been painted over, so it may not lift out for cleaning.
Why it matters
A blocked drain cannot carry away a leak or flood water. A dry trap can also let sewer odour in.
What to do
Free and clean the grate and test the drain with a bucket of water. Pour water into it every few months to keep the trap sealed.
Who to call
Homeowner or plumber
Painted, partly clogged floor drain
Photo 35.1Painted, partly clogged floor drain
36

Toilet tank depositsBasement bathroom

Maintenance
What we found
There are dark deposits inside the toilet tank.
Why it matters
Deposits wear the flapper and flush valve, which leads to a running toilet.
What to do
Clean the tank and replace the flapper if it leaks.
Who to call
Handyman
Inside the tank
Photo 36.1Inside the tank
Section 6 of 10

Electrical

8 Safety2 Maintenance

About this system

ServiceOverhead service drop to a through-roof mast on the driveway side; meter on the driveway-side wall.
PanelITE "BL Loadcenter" in the basement utility room; panel rated 125 A, with a 100 A double-pole main breaker; 120/240 V single phase; 24 positions, all in use.
Branch wiringA mix: modern white NMD sheathed cable alongside older black and cloth-covered cables. Whether any knob-and-tube wiring remains hidden in the walls could not be determined.
ReceptaclesA mix of grounded three-slot and older two-slot receptacles. GFCI protection only at the basement bathroom (it worked).
Smoke and CO alarmsOne working smoke alarm at the basement stairs; the others are defective (see finding). No CO alarms found.
Main panel
Main panel

Findings (10)

37

Smoke alarms not working; no carbon monoxide alarmsMain-floor hallway, upper floor, whole house

Safety
What we found
The upper-floor smoke alarm, the only one on that floor, did not sound when tested. On the main-floor hallway alarm the test button stuck, and the alarm kept sounding after it was pressed. Both units look older. The basement-stairs alarm worked. We found no CO alarms, although the house has a gas furnace.
Why it matters
Working alarms are the most important life-safety devices in a home. Ontario's Fire Code requires a working smoke alarm on every storey and outside all sleeping areas. In homes with a fuel-burning appliance, it requires CO alarms next to each sleeping area and, since 1 January 2026, on every storey, including storeys without bedrooms.
What to do
Before moving in, replace the defective smoke alarms and any that are more than 10 years old. Install CO alarms on every storey, including the basement, and next to each sleeping area; combination smoke/CO units can do both. Interconnected alarms are a worthwhile upgrade, especially if the basement is occupied separately.
Who to call
Homeowner, or an electrician for hard-wired alarms
Upper-floor alarm that did not sound
Photo 37.1Upper-floor alarm that did not sound
Hallway alarm with stuck test button
Photo 37.2Hallway alarm with stuck test button
Basement-stairs alarm (worked)
Photo 37.3Basement-stairs alarm (worked)
38

No GFCI protection detected at the kitchen countersMain-floor kitchen (both receptacles beside the sink) and basement kitchen (counter receptacles about 3 ft and 3.5 ft from the sink)

Safety
What we found
GFCI protection was not detected at the counter receptacles near either kitchen sink. Pressing the test button on a plug-in GFCI tester did not trip any device, and no GFCI receptacle or GFCI breaker serving them was found. On one basement receptacle only one slot could be tested.
Why it matters
GFCI protection cuts power within milliseconds if current leaks to ground, for example through a person touching water. It was not required when the house was built, but current Canadian Electrical Code rules require it for receptacles within 1.5 m of a sink, and it is a recommended safety upgrade.
What to do
Have a licensed electrician add GFCI protection to all receptacles near sinks and outdoors.
Who to call
Licensed electrician
Main-floor kitchen: receptacles beside the sink
Photo 38.1Main-floor kitchen: receptacles beside the sink
Basement kitchen: receptacle about 3 ft from the sink
Photo 38.2Basement kitchen: receptacle about 3 ft from the sink
Basement kitchen: receptacle about 3.5 ft from the sink
Photo 38.3Basement kitchen: receptacle about 3.5 ft from the sink
39

Exterior GFCI receptacle does not tripLeft side of the house, exterior wall

Safety
What we found
The outdoor receptacle is a GFCI type, but it did not trip when its test button was pressed or when tested with a GFCI tester. The receptacle and its weatherproof cover are aged, and the masonry around the box has been patched.
Why it matters
An outdoor receptacle without working ground-fault protection is a shock hazard.
What to do
Have it replaced with a weather-resistant GFCI receptacle and an in-use (bubble) cover sealed to the wall.
Who to call
Licensed electrician
Exterior GFCI that failed the test
Photo 39.1Exterior GFCI that failed the test
40

Open-ground and reversed-polarity receptaclesUpper bedroom 4, upper bedroom 3, small upper room, main-floor bedroom 2 (open ground); main-floor bedroom 1 (hot and neutral reversed)

Safety
What we found
Receptacles in four rooms tested as open ground: they accept a three-prong plug but have no ground connection. Bedroom 4 has only old two-slot receptacles, one of them fitted so that it accepts a three-prong plug, and it is painted over. In main-floor bedroom 1, a receptacle tested with hot and neutral reversed.
Why it matters
An ungrounded three-slot receptacle gives a false sense of protection to appliances that need a ground. Reversed polarity can leave parts of a plugged-in device live even when it is switched off.
What to do
Have an electrician test every receptacle and correct the wiring. Ungrounded circuits can be rewired, or protected with GFCI devices and labelled "No equipment ground", as the Code allows.
Who to call
Licensed electrician
Bedroom 4: open ground
Photo 40.1Bedroom 4: open ground
Bedroom 4: old receptacle, painted over
Photo 40.2Bedroom 4: old receptacle, painted over
Main-floor bedroom 1: hot and neutral reversed
Photo 40.3Main-floor bedroom 1: hot and neutral reversed
Main-floor bedroom 2: open ground
Photo 40.4Main-floor bedroom 2: open ground
41

Mixed and older wiring, loose conductors at the panelBasement utility room, at and above the electrical panel

Safety
What we found
Old and new wiring types run together above the panel, including older black and cloth-covered cables. There are loose conductor ends that are not terminated in covered junction boxes. The cables crowd into the side of the panel, and a device with exposed wiring is mounted beside it. Some cables pass through roughly notched joists.
Why it matters
We could not confirm whether the loose conductors are energized, so treat them as live until an electrician confirms otherwise. Exposed or unterminated conductors are a shock and fire hazard. Older insulation becomes brittle with age, and some insurers ask about older wiring before they will cover a house.
What to do
Have a licensed electrical contractor review the panel and the visible wiring, make the loose ends safe, put splices in covered boxes, identify the unknown device, and advise on replacing any older wiring that is still in use.
Who to call
Licensed electrical contractor
Old and new cables above the panel; notched joist
Photo 41.1Old and new cables above the panel; notched joist
Loose cables and conductors
Photo 41.2Loose cables and conductors
Crowded cable entries and the adjacent device
Photo 41.3Crowded cable entries and the adjacent device
42

Makeshift wiring on top of the water heaterBasement utility room, top of the electric water heater

Safety
What we found
A loose porcelain lamp holder lies on top of the water heater, attached to an aged cable that is taped and has deteriorated insulation.
Why it matters
Exposed live parts and damaged cable next to plumbing are a shock and fire hazard.
What to do
Have an electrician remove the lamp holder or install it properly in a box, and check the water heater's supply cable and connection.
Who to call
Licensed electrician
Loose lamp holder and taped cable on top of the tank
Photo 42.1Loose lamp holder and taped cable on top of the tank
Deteriorated cable at the lamp holder
Photo 42.2Deteriorated cable at the lamp holder
43

Discoloured receptacle behind the washerBasement laundry area, behind the washing machine

Safety
What we found
The receptacle next to the washer's plug has dark, scorch-like discolouration around its slots.
Why it matters
Discolouration like this can mean the receptacle has overheated because of a loose connection.
What to do
Stop using it until an electrician has checked and replaced it.
Who to call
Licensed electrician
Dark discolouration at the receptacle
Photo 43.1Dark discolouration at the receptacle
44

Panel full; circuit directory incompleteBasement utility room

Maintenance
What we found
All 24 breaker positions are used, so there is no room for new circuits. The circuit directory is only partly filled in.
Why it matters
Adding circuits (for example an EV charger, a heat pump or a renovation) will need panel work, and an unlabelled panel slows things down in an emergency.
What to do
Have the circuits traced and labelled. If you plan to add significant loads, ask an electrician about a load calculation and a panel or service upgrade.
Who to call
Licensed electrician
Partly completed directory
Photo 44.1Partly completed directory
100 A main breaker; all positions in use
Photo 44.2100 A main breaker; all positions in use
45

Receptacle missing its cover plateBasement family room, lower side of the central column

Safety
What we found
A receptacle on the lower side of the central column is missing its cover plate.
Why it matters
Without a cover plate, live terminals and wiring are within reach, at a height a child could reach.
What to do
Fit a cover plate. It is an inexpensive fix, but do it before moving in.
Who to call
Homeowner or electrician
46

Basement shower light not workingBasement bathroom

Maintenance
What we found
The light in the shower area did not work. The bulb may be burned out.
Why it matters
A dark shower area is a slip risk.
What to do
Replace the bulb, and have an electrician check the fixture if it still does not work. It sits over a shower, so it should be rated for damp locations.
Who to call
Homeowner or electrician
Shower light that did not work
Photo 46.1Shower light that did not work
Section 7 of 10

Attic and insulation

1 Repair1 Maintenance

About this system

AccessThrough the knee-wall access panels in upper bedroom 4 and the small upper room. There is no other attic hatch.
How inspectedBoth panels were opened and the attic spaces were inspected from the openings with a flashlight, a camera and the thermal camera. The attic was not entered: the inspector judged it unsafe, because there is no floor or walkway (only insulation over open joists), there are loose boards and debris, and headroom is tight. Areas beyond view from the openings, including the far ends of the knee-wall spaces and any space above the upper ceilings, were not inspected.
InsulationOlder fibreglass batts in the knee walls, and loose-fill and batt fibreglass in the attic floor.
VentilationStatic box vents on both slopes and vented soffits at the gables. We could not confirm whether intake and exhaust are balanced.
NoteNail tips poking through the roof boards are normal and not a defect.

Findings (2)

47

Attic insulation displaced, stained and below current levels; dark staining on the roof boardsAttic spaces behind the upper-floor knee walls

Repair
What we found
The knee-wall batts are old and heavily stained black and grey, with no air barrier over them. In the attic floor, the insulation is thin, matted and displaced, with the tops of the joists exposed, and there is torn paper and debris. The roof boards and rafters have dark staining in several areas.
Why it matters
Dark streaks in fibreglass usually come from house air leaking through it over many years, which wastes heat and can cause condensation. The staining on the roof boards could be from past roof leaks (the current shingles look sound), condensation, or older damage. Matted insulation can also be a sign of past animal activity. The thermal image of bedroom 3 shows the cold patches you would expect.
What to do
Ask the seller about any past roof leaks, fire or animal problems in the attic. Have an insulation contractor remove the damaged material, air-seal the knee walls and ceiling, add insulation to current levels, and check the ventilation. Have a roofer look at any roof boards that are still soft or stained after that work.
Who to call
Insulation contractor; roofer if needed
Knee-wall batts: heavy dark staining, no air barrier
Photo 47.1Knee-wall batts: heavy dark staining, no air barrier
Displaced, matted insulation; exposed joists
Photo 47.2Displaced, matted insulation; exposed joists
Torn paper, debris and stained rafters
Photo 47.3Torn paper, debris and stained rafters
Dark staining on the roof boards (nail tips are normal)
Photo 47.4Dark staining on the roof boards (nail tips are normal)
Thermal: banded cold areas in the sloped ceiling, bedroom 4
Photo 47.5Thermal: banded cold areas in the sloped ceiling, bedroom 4
48

Attic access panels not insulated or weatherstrippedUpper bedroom 4 and the small upper room

Maintenance
What we found
The knee-wall access panels are uninsulated, have no weatherstripping, and are held only by wing nuts. One panel frame is chipped.
Why it matters
Warm, moist house air leaks into the cold attic around the panels.
What to do
Insulate the back of each panel and fit weatherstripping and latches that pull it tight.
Who to call
Handyman or insulation contractor
Bedroom 4 access panel
Photo 48.1Bedroom 4 access panel
Panel opened to the attic
Photo 48.2Panel opened to the attic
Small upper room access panel
Photo 48.3Small upper room access panel
Section 8 of 10

Interior

3 Safety3 Repair5 Maintenance1 Monitor

About this system

LayoutMain floor: living room, dining area, eat-in kitchen, two bedrooms and a bathroom. Upper floor: two bedrooms and a small storage room. Basement: family room, second kitchen, bathroom, laundry, utility room and cold room, with a separate side entrance.
Central vacuumAn Electrolux central vacuum power unit is in the utility room, although the listing says there is no central vacuum. It was not tested.
FinishesHardwood, carpet, vinyl and ceramic tile floors; plaster or drywall walls and ceilings.
WindowsMostly replacement sliding and hung windows; aluminum awnings outside.
Room namesThis report uses the room names on the floor-plan page at the back.

Findings (12)

49

Capped pipe sticking up through the floorSmall upper room (1.58 × 1.16 m), carpeted floor near the wall

Safety
What we found
A capped threaded pipe stands several centimetres above the carpet next to the wall. It is corroded, and there is dark staining along the base of the wall beside it. It may be an old gas or heating line, but we could not confirm what it is.
Why it matters
It is a trip hazard. If it is an old gas line, it needs to be confirmed as disconnected and properly capped.
What to do
Have a TSSA-registered gas contractor identify the pipe and confirm that it is isolated, or remove it. Have the area checked for moisture.
Who to call
TSSA-registered gas contractor
Capped pipe through the carpet
Photo 49.1Capped pipe through the carpet
Its location by the wall
Photo 49.2Its location by the wall
50

Upper floor may lack an emergency escape windowUpper floor (bedrooms 3 and 4); also noted in main-floor bedroom 1

Safety
What we found
In upper bedroom 4 the single opening sash measured about 16 × 26 in (about 0.27 m²). The bedroom 3 window did not open easily and was not measured. The window in main-floor bedroom 1 also has a small opening, but the main floor has exterior doors.
Why it matters
The upper floor has one stair and no exterior door, so in a fire a window may be the only other way out. The current Ontario Building Code, which applies to new construction and renovations, requires each floor level that contains a bedroom (unless it has a door leading directly outside) to have at least one window with an unobstructed opening of at least 0.35 m², no dimension under 380 mm, that opens from inside without tools. Bedroom 4's window is below that size. Existing homes are not required to be upgraded, but the risk is real.
What to do
Measure the bedroom 3 window opening. Consider fitting at least one larger opening window on the upper floor when windows are replaced, and keep the stairs and hall clear. Working, interconnected smoke alarms matter even more here.
Who to call
Window contractor
Upper bedroom 3
Photo 50.1Upper bedroom 3
Main-floor bedroom 1 window
Photo 50.2Main-floor bedroom 1 window
51

Dryer exhaust duct is soft plasticBasement laundry area, in the cabinet above the dryer

Safety
What we found
The dryer exhausts through a soft white plastic flexible duct running up through the cabinet shelves. The duct is brittle and close to breaking. The dryer is an older unit.
Why it matters
Plastic ducts trap lint and can melt or burn. They are a known cause of dryer fires, and dryer manufacturers' installation instructions call for metal duct.
What to do
Replace it with rigid or semi-rigid metal duct, as short and straight as possible, ending outside in a hooded damper. Clean the lint from the run.
Who to call
HVAC contractor or appliance technician
Plastic dryer duct inside the cabinet
Photo 51.1Plastic dryer duct inside the cabinet
52

Old laundry exhaust fan open to the outdoorsBasement laundry area

Repair
What we found
The through-wall exhaust fan is an old unit with corroded parts. Daylight shows through its grille because there is no damper, and the wall below it is stained and cracked.
Why it matters
Cold air, insects and moisture get in, and old motors and wiring can overheat.
What to do
Replace it with a modern exhaust fan that has a backdraft damper and an exterior hood, and seal the opening.
Who to call
Electrician or HVAC contractor
Old fan with daylight through the grille
Photo 52.1Old fan with daylight through the grille
Thermal: cold air spilling down the wall below the fan
Photo 52.2Thermal: cold air spilling down the wall below the fan
53

Open hole in the wall behind the basement kitchen cabinetBasement kitchen, inside the upper cabinet

Repair
What we found
A large rough opening in the back of the cabinet exposes the wall cavity, the drain piping and displaced foam insulation.
Why it matters
It lets air and moisture move freely into the wall cavity. If this wall is meant to be a fire separation (for example between two units), an opening would compromise it.
What to do
Restore the wall enclosure and insulation, and have the contractor determine whether fire-rated construction is required here. Ask the seller what work was done.
Who to call
General contractor
Opening inside the cabinet
Photo 53.1Opening inside the cabinet
Drain piping and insulation in the cavity
Photo 53.2Drain piping and insulation in the cavity
54

Living room window frame damaged; possible failed sealLiving room, front window

Repair
What we found
The window frame is damaged. The upper glass looked hazy or speckled, which can mean the seal between the panes has failed. The window does operate.
Why it matters
A failed seal lets moisture between the panes and reduces their insulating value.
What to do
Have a window contractor repair the frame and confirm the seal, replacing the sealed glass unit if needed.
Who to call
Window contractor
Living room window
Photo 54.1Living room window
55

Main-floor bedroom 2: window caulking and closet wallMain-floor bedroom 2: window, and the closet wall shared with the bathroom

Maintenance
What we found
The finish is peeling along the window jamb, and there is a crack and gap at the corner where the jamb meets the sill. Inside the closet, the wall shared with the bathroom has patched, bubbled areas that look like past moisture.
Why it matters
Gaps let in drafts and water. The closet wall is directly behind the bathroom that has no exhaust fan and worn tub joints.
What to do
Seal and refinish the window. Check the closet wall with a moisture meter, then repair and repaint it once the bathroom work is done.
Who to call
Handyman; painter
Cracked jamb and peeling finish
Photo 55.1Cracked jamb and peeling finish
Gap at the sill corner
Photo 55.2Gap at the sill corner
Closet wall: past moisture marks
Photo 55.3Closet wall: past moisture marks
56

Upper bedroom 3: hole in the wall and a gap at the trimUpper bedroom 3, beside the window

Maintenance
What we found
There is a small hole and crack in the wall beside the window, and a gap between the window trim and the wall.
Why it matters
Air leaks at gaps like these add to the cold areas the thermal camera showed in this room.
What to do
Patch and repaint, and seal the trim.
Who to call
Handyman
Hole beside the window
Photo 56.1Hole beside the window
Gap at the window trim
Photo 56.2Gap at the window trim
57

Upper bedroom 4: window sill finish peelingUpper bedroom 4

Maintenance
What we found
The finish on the window sill is peeling and chipped.
Why it matters
Mainly cosmetic, though older paint may contain lead.
What to do
Test before sanding, then refinish.
Who to call
Painter
Peeling sill
Photo 57.1Peeling sill
58

Several windows stickMain-floor bathroom, basement bathroom, upper bedroom 3

Maintenance
What we found
These windows are jammed or hard to open.
Why it matters
Windows that will not open limit ventilation and, in bedrooms, escape.
What to do
Clean and lubricate the tracks and adjust or repair the hardware.
Who to call
Handyman or window contractor
59

Basement bathroom fan works only with the heat-lamp lightBasement bathroom ceiling

Maintenance
What we found
The exhaust fan is built into a heat-lamp light fixture and runs only when the light is on.
Why it matters
If the fan is not run long enough after a shower, moisture stays in the room. Whether it vents outside was not confirmed.
What to do
Confirm that it vents outdoors. Consider a separately switched fan on a timer.
Who to call
Electrician
Combined fan and heat lamp
Photo 59.1Combined fan and heat lamp
60

Hairline crack in the living room ceilingLiving room ceiling

Monitor
What we found
There is a long hairline crack in the plaster ceiling.
Why it matters
This is typical of older plaster as the house settles and as temperature and humidity change. It is not a structural concern by itself.
What to do
Monitor it, and repair it cosmetically when you next paint.
Who to call
Painter or plasterer
Hairline ceiling crack
Photo 60.1Hairline ceiling crack
Section 9 of 10

Appliances

1 Safety

About this system

ScopeAppliances were run briefly with their normal controls, as a courtesy. This is not a full evaluation.
Range hoodThe basement kitchen range hood ran normally.
PresentGas range in the main-floor kitchen (listed as a gas stove), electric range in the basement kitchen, two refrigerators, washer and dryer.

Findings (1)

61

Range anti-tip bracket missing on the basement rangeBasement kitchen range (not confirmed on the main-floor range)

Safety
What we found
No anti-tip bracket was found on the basement electric range, and one was not visible on the main-floor gas range.
Why it matters
A freestanding range can tip forward if someone leans or stands on the open oven door, a known cause of serious injuries to children.
What to do
Install an anti-tip bracket on the basement range, and check the main-floor range and fit one if it is missing. They are inexpensive and often supplied with the range.
Who to call
Appliance installer or handyman
Basement kitchen range
Photo 61.1Basement kitchen range
Section 10 of 10

Detached garage

2 Safety3 Repair1 Monitor

About this system

ConstructionDetached garage, about 20 × 20 ft (listed as a double garage), with one vehicle door, brick front, concrete block walls, wood-framed roof with board/OSB sheathing, concrete slab.
Vehicle doorWood sectional door with an electric opener.
LimitsStored belongings blocked parts of the walls, floor and ceiling.
Garage interior
Garage interior

Findings (6)

62

Garage door opener has no photo-eye safety sensorsGarage vehicle door

Safety
What we found
The opener has no photo-eye sensors near the floor. The door did reverse when it met resistance while closing, but nothing would stop it closing on a person, child or pet that is in its path without touching it.
Why it matters
Photo-eye sensors have been standard for decades because closing garage doors have caused serious injuries and deaths.
What to do
Have the opener fitted with photo-eye sensors mounted no more than 6 in (15 cm) above the floor, or replaced. Have the technician confirm the auto-reverse using the manufacturer's test (usually a 2×4 laid flat under the door). The door springs are under high tension: do not adjust them yourself.
Who to call
Garage door technician
Garage vehicle door
Photo 62.1Garage vehicle door
Door open: no sensors at the track bases
Photo 62.2Door open: no sensors at the track bases
63

Garage block wall: open joint, cracked mortar, damp wallsGarage walls

Repair
What we found
One vertical joint in the block wall is open right through, and daylight shows through it. The mortar around it is cracked. Inside, the block walls are stained, which shows they have been wet.
Why it matters
Water, cold and pests get in. Cracks that keep widening would mean the wall is moving.
What to do
Have a mason repoint and seal the joint and cracks. Fix the downspout and grading outside, and monitor the cracks for change.
Who to call
Mason
Open vertical joint (daylight visible)
Photo 63.1Open vertical joint (daylight visible)
Cracked mortar around the joint
Photo 63.2Cracked mortar around the joint
Stained interior block wall
Photo 63.3Stained interior block wall
Damp staining in a corner
Photo 63.4Damp staining in a corner
64

Garage downspout empties toward the foundationGarage exterior, rear corner

Repair
What we found
The downspout is bent and ends in an improvised extension that turns back toward the garage wall, where the ground is low. A corroded bracket and pipe on the wall behind it may be leftovers.
Why it matters
Roof water is being directed against the block wall and is a likely contributor to the staining inside.
What to do
Repair the downspout and extend it at least 1.8 m (6 ft) from the wall, regrade the ground, and remove any hardware that is no longer needed.
Who to call
Handyman or eavestrough contractor
Downspout returning toward the wall
Photo 64.1Downspout returning toward the wall
65

Garage doors and trim weathered; split door panelGarage pedestrian door, vehicle door and their trim

Repair
What we found
The pedestrian door and its frame have heavy peeling and weathered wood. The vehicle-door trim has peeling paint and broken wood at the bottom, and one panel of the wood vehicle door is split open.
Why it matters
Bare wood rots, and a split panel weakens the door.
What to do
Repair the split panel and the rotted trim, then prime and paint. Have the door's balance and operation checked at the same visit.
Who to call
Carpenter; garage door technician
Pedestrian door
Photo 65.1Pedestrian door
Split panel in the vehicle door
Photo 65.2Split panel in the vehicle door
Vehicle door and trim
Photo 65.3Vehicle door and trim
66

Garage ceiling wiring is makeshift; roof sheathing stainedGarage ceiling

Safety
What we found
Open-bulb lights and loose cable runs are strung across the open ceiling framing, and the door opener is plugged into a ceiling receptacle. There is dark staining on the underside of the roof sheathing.
Why it matters
The cables are loose and unprotected where they can be reached and damaged, which is a shock and fire hazard. The staining may come from past roof leaks or condensation.
What to do
Have an electrician secure and box the wiring and confirm the circuit protection. Have the roof checked when the garage is re-shingled.
Who to call
Licensed electrician; roofer
Ceiling framing, lights and wiring
Photo 66.1Ceiling framing, lights and wiring
Stained sheathing
Photo 66.2Stained sheathing
67

Garage floor crackGarage floor, running to the entrance

Monitor
What we found
A crack runs through the garage slab to the entrance. We saw no displacement between its sides.
Why it matters
Cracks like this are common in garage slabs. Widening or one side dropping would point to settlement.
What to do
Monitor it, and seal it to keep water and salt out.
Who to call
Concrete contractor if it changes
Slab crack
Photo 67.1Slab crack
Appendix A

Thermal imaging

Thermal imaging was done with a handheld infrared camera (HIKMICRO B10S, emissivity 0.95) as an extra, non-invasive screening tool. About 40 thermal images were taken, each paired with an ordinary photo, covering the upper bedrooms, the attic access, the basement and the main floor. Conditions were only moderately favourable: about 22 °C inside and 7.8 °C outside, a difference of about 14 °C, with afternoon sun warming some walls and doors. Most temperature differences were small. A thermal camera shows surface temperatures only, so a cold or warm pattern is not proof of a defect; it shows where to look more closely.

68

Thermal imaging: cold areas in the upper bedroomsUpper bedrooms 3 and 4: sloped ceilings and knee walls

Monitor
What we found
In both upper bedrooms, the sloped ceilings and knee walls show cooler bands between the framing and cool lines at the wall-to-ceiling junction, at about 10.6 to 14 °C against roughly 17 °C elsewhere on the same surfaces. The pinless meter showed no elevated relative reading at the cool spots; a pin-type meter was not permitted.
Why it matters
This pattern is typical of thin, missing or displaced insulation and air leakage in a 1½-storey roof, which is what the attic finding describes. The meter results did not point to moisture.
What to do
No separate repair. This is handled by the attic insulation and air-sealing work. A follow-up scan after that work will confirm the improvement.
Who to call
Insulation contractor
Bedroom 3: cool bands and a cool wall-to-ceiling junction
Photo 68.1Bedroom 3: cool bands and a cool wall-to-ceiling junction
Same view, ordinary photo
Photo 68.2Same view, ordinary photo
Bedroom 4: cooler bays in the sloped ceiling
Photo 68.3Bedroom 4: cooler bays in the sloped ceiling
Same view, ordinary photo
Photo 68.4Same view, ordinary photo

Thermal scan log

AreaTimeResult
Attic access and upper bedroom 410:50, 10:54, 10:55, 10:55, 10:55, 10:55Banded cool areas in the sloped ceilings and knee walls (about 10.6–14 °C). Warm spots are the light fixtures. Consistent with the attic insulation finding.
Upper bedroom 311:26, 11:27, 11:30Cool bands and a cool wall-to-ceiling junction (about 10.6–14 °C). No elevated relative reading at the cool spots on the pinless meter.
Small upper room, knee-wall panel11:33, 11:33A slight temperature difference around the uninsulated access panel and at the outside corner. Minor.
Basement kitchen13:57, 13:57No anomaly at the sink wall or under the cabinets. The window is cooler, as expected.
Closet under the basement stairs13:58, 13:58Cooler, blotchy areas on the foundation wall (about 7–11 °C) matching the damp, flaking areas; the cold water pipe is visible. Supports the moisture finding.
Basement family room13:58, 13:58, 13:58No anomalies. Warm spots are the pot lights.
Basement bathroom13:59, 13:59The toilet tank is cool (cold water), which is normal. No distinct pattern at the floor; the moisture-meter readings are the stronger evidence there.
Laundry area14:00, 14:00, 14:00Cold air spilling down the wall below the old through-wall exhaust fan. Supports the laundry-fan finding.
Cold room14:00, 14:01, 14:01Unheated space at about 5–10 °C, as expected. The door into it is cold, which shows it is uninsulated.
Main-floor bedroom 114:03, 14:04, 14:04, 14:04Window sashes are cooler, which is normal for windows. A slight cool line at the top of the exterior wall at the ceiling. Minor.
Side and front entrances14:55, 14:55Cold edges along the bottom and latch side of the side door, which supports the weatherstripping finding. The front door is sun-warmed.
Main-floor hall and kitchen14:55, 14:55No anomalies.
Main-floor bathroom14:55, 14:55, 14:56No cold or wet pattern at the tub-to-floor joint or around the toilet. The toilet is cool from its water, which is normal.
Living room14:56, 14:57, 14:57Faint vertical stripes on the exterior wall from the framing behind the plaster, and a slightly cooler area at the ceiling edge. Typical; no moisture pattern.

Selected thermal and visual pairs

Closet under the stairs: cooler, blotchy damp areas (thermal)
Photo A.1Closet under the stairs: cooler, blotchy damp areas (thermal)
Same view, ordinary photo
Photo A.2Same view, ordinary photo
Laundry: cold air below the exhaust fan (thermal)
Photo A.3Laundry: cold air below the exhaust fan (thermal)
Same view, ordinary photo
Photo A.4Same view, ordinary photo
Side entrance door: cold edges (thermal)
Photo A.5Side entrance door: cold edges (thermal)
Same view, ordinary photo
Photo A.6Same view, ordinary photo
Main bathroom tub-to-floor joint: no anomaly (thermal)
Photo A.7Main bathroom tub-to-floor joint: no anomaly (thermal)
Same view, ordinary photo
Photo A.8Same view, ordinary photo
Living room exterior wall: framing pattern only (thermal)
Photo A.9Living room exterior wall: framing pattern only (thermal)
Same view, ordinary photo
Photo A.10Same view, ordinary photo
Main-floor bedroom 1: no anomaly (thermal)
Photo A.11Main-floor bedroom 1: no anomaly (thermal)
Same view, ordinary photo
Photo A.12Same view, ordinary photo
Appendix B

Floor plans and room names

Floor plans made with the CubiCasa app and relabelled by JBM Inspect to match the room names in this report. Numbered markers show where each finding was observed (positions are approximate); the roof and gutters (findings 1 to 6), the driveway (16) and the detached garage (62 to 67) are not on the plans. Measurements are approximate. Total about 212 m² (basement 91 m², main floor 75 m², upper floor 46 m²).

Main floor floor plan with numbered markers showing where findings were observed
Floor plan

Main floor

Bedroom 1
The larger main-floor bedroom (3.40 × 4.38 m), at the rear. The listing calls it the primary bedroom.
Bedroom 2
The smaller main-floor bedroom (2.81 × 2.91 m), at the rear next to the bathroom. The listing calls it the 2nd bedroom.
Bath
Main-floor bathroom (4-piece, tub and shower). It has no exhaust fan.
Eat-in kitchen
Main-floor kitchen, with the gas range.
Foyer
Front entrance. The stairs beside it go up to the upper floor and down to the side entrance and basement.
Upper floor floor plan with numbered markers showing where findings were observed
Floor plan

Upper floor

Bedroom 3
Rear upper bedroom (3.59 × 3.37 m). The listing calls it the 3rd bedroom.
Bedroom 4
Front upper bedroom (3.59 × 5.25 m), the larger one. The listing calls it the 4th bedroom; the floor-plan app had labelled it "Primary bedroom".
Small room
The 1.58 × 1.16 m room off the upper hall. It has no window or heat, so it is not a bedroom. The capped pipe and one attic access panel are here.
Attic access
Knee-wall access panels in bedroom 4 and the small room lead to the attic spaces behind the sloped walls.
Basement floor plan with numbered markers showing where findings were observed
Floor plan

Basement

Cold room
The unheated room (5.30 × 2.99 m) under the rear concrete patio. The listing calls it the cold room or cantina.
Utility
Furnace, air-conditioning coil, humidifier, water heater, electrical panel and central vacuum unit.
Laundry
Washer, dryer and laundry sink.
Bath
Basement bathroom (3-piece, shower).
Kitchen
Basement kitchen, with the electric range.
Closet under the stairs
The closet with the water meter and main water shut-off, beside the basement stairs. It is not labelled on the plan.
Sign-off

Thank you

Thank you for choosing JBM Inspect. Please read the whole report, not only the summary, and call me with any questions, whether before closing or after you move in.

Jit Makim, CPI
JBM Inspect · (437) 227-6800 · contact@jbminspect.ca · jbminspect.ca
InterNACHI Certified Professional Inspector (CPI) · PITI Level I Infrared Building Surveyor · Transport Canada Advanced RPAS Pilot

׋›